MP3100 Series 3/1 Phase UPS

Cabinet power range 80 kVA, 100 kVA and 120 kVA.

MP3100 series on-line intelligent digital UPS agglomerates the essence of Baykee techniques and entirely break through the bottleneck technology in traditional simulation circuit age.

It adopts the digital control technology, of which the core is high-speed MCU and programmable logic device (CPLD). It brings in the sixth generation low-exhaust and big-power IGBT module and static switch as power devices.

It is really the highlight product which is guided by these most advanced technologies all over the world.

ModelMP3180KMP31100KMP31120K
Capacity80kVA100kVA120kVA
Power Watt64kW80kW96kW
Working PrincipalLow-Frequency Transformer Based True On Line-Double ConversionLow-Frequency Transformer Based True On Line-Double ConversionLow-Frequency Transformer Based True On Line-Double Conversion
RECTIFIER (INPUT)
PhaseThree PhaseThree PhaseThree Phase
Input Power FactorStandard greater than 0.9 (6 Pulse rectifier + Filter)
Optional greater than 0.96 (12 Pulse rectifier + Filter)
Standard greater than 0.9 (6 Pulse rectifier + Filter)
Optional greater than 0.96 (12 Pulse rectifier + Filter)
Standard greater than 0.9 (6 Pulse rectifier + Filter)
Optional greater than 0.96 (12 Pulse rectifier + Filter)
Input Voltage Range220 / 380VAC (230V / 400VAC or 240V / 415VAC) ±25% 3P+N+PE

110V / 208VAC (120V / 220VAC or 277V / 480VAC) optional

220 / 380VAC (230V / 400VAC or 240V / 415VAC) ±25% 3P+N+PE

110V / 208VAC (120V / 220VAC or 277V / 480VAC) optional

220 / 380VAC (230V / 400VAC or 240V / 415VAC) ±25% 3P+N+PE

110V / 208VAC (120V / 220VAC or 277V / 480VAC) optional

Input Frequency Range50Hz ±10%
60Hz ±10% (Selectable)
50Hz ±10%
60Hz ±10% (Selectable)
50Hz ±10%
60Hz ±10% (Selectable)
Output RippleLess than 2%Less than 2%Less than 2%
Soft Start0 up to 100% 5sec0 up to 100% 5sec0 up to 100% 5sec
CHARGING
Charging ModeConstant current, then constant voltage. Charge with temperature compensation, automatic switch between equalized charging and float charging.Constant current, then constant voltage. Charge with temperature compensation, automatic switch between equalized charging and float charging.Constant current, then constant voltage. Charge with temperature compensation, automatic switch between equalized charging and float charging.
Float Charging Voltage405VDC405VDC405VDC
Equalized Charging Voltage432VDC432VDC432VDC
Temp. Compensated

Voltage

-3mV / ℃ / Cell-3mV / ℃ / Cell-3mV / ℃ / Cell
Charging Current0.1C (Automatic adjust according to battery capacity)0.1C (Automatic adjust according to battery capacity)0.1C (Automatic adjust according to battery capacity)
BATTERY
TypeVRLA / AGM / Gel,
optional Lithium Battery
VRLA / AGM / Gel,
optional Lithium Battery
VRLA / AGM / Gel,
optional Lithium Battery
Battery Capacity7 up to 999AH settable (Configure Battery Capacity according to Back-up Time)7 up to 999AH settable (Configure Battery Capacity according to Back-up Time)7 up to 999AH settable (Configure Battery Capacity according to Back-up Time)
Quantity30 units 12V or 180 units 2V batteries (Nominal Voltage 384VDC)30 units 12V or 180 units 2V batteries (Nominal Voltage 384VDC)30 units 12V or 180 units 2V batteries (Nominal Voltage 384VDC)
Temperature20ºC up to 25ºC (For Maximum Efficiency)20ºC up to 25ºC (For Maximum Efficiency)20ºC up to 25ºC (For Maximum Efficiency)
INVERTER (OUTPUT)
PhaseSingle PhaseSingle PhaseSingle Phase
Rated VoltageRated Capacity * 0.9Rated Capacity * 0.9Rated Capacity * 0.9
Nominal Voltage220VAC (230VAC or 240VAC), 1P+N

110V (120V or 277V) optional

220VAC (230VAC or 240VAC), 1P+N

110V (120V or 277V) optional

220VAC (230VAC or 240VAC), 1P+N

110V (120V or 277V) optional

Output Voltage Regulated Accuracy±1% (Stable load)
±3% (Fluctuant load)
±1% (Stable load)
±3% (Fluctuant load)
±1% (Stable load)
±3% (Fluctuant load)
Output Frequency Range50Hz – 60Hz less than ±0.5% (Asynchronous)50Hz – 60Hz less than ±0.5% (Asynchronous)50Hz – 60Hz less than ±0.5% (Asynchronous)
Crest FactorGreater than 3:1Greater than 3:1Greater than 3:1
Output Total Harmonic

Distortion (THD)

Pure Sine Wave
Linear Load less than 3%
Non-Linear Load less than 5%
Pure Sine Wave
Linear Load less than 3%
Non-Linear Load less than 5%
Pure Sine Wave
Linear Load less than 3%
Non-Linear Load less than 5%
Dynamic CharacteristicsInstant voltage less than ±5% (0 – 100%)
Instant recover time less than 10ms
Instant voltage less than ±5% (0 – 100%)
Instant recover time less than 10ms
Instant voltage less than ±5% (0 – 100%)
Instant recover time less than 10ms
Unbalanced Load VoltageLess than ±5%Less than ±5%Less than ±5%
Overload CapacityAt 115% load, normal work
At 125% load 10min
At 150% load 1min
At 200% load 1sec
At 115% load, normal work
At 125% load 10min
At 150% load 1min
At 200% load 1sec
At 115% load, normal work
At 125% load 10min
At 150% load 1min
At 200% load 1sec
Inverter EfficiencyGreater than 93% (full load)Greater than 93% (full load)Greater than 93% (full load)
BYPASS
PhaseSingle PhaseSingle PhaseSingle Phase
Input Nominal Voltage220 / 380VAC (230V / 400VAC or 240V / 415VAC)

110V (120V or 277V) optional

220 / 380VAC (230V / 400VAC or 240V / 415VAC)

110V (120V or 277V) optional

220 / 380VAC (230V / 400VAC or 240V / 415VAC)

110V (120V or 277V) optional

Output Nominal Voltage220VAC (230VAC or 240VAC)

110V (120V or 277V) optional

220VAC (230VAC or 240VAC)

110V (120V or 277V) optional

220VAC (230VAC or 240VAC)

110V (120V or 277V) optional

Transfer Time0ms (adopt static switch)0ms (adopt static switch)0ms (adopt static switch)
PROTECTION FUNCTION
Input ProtectionInput voltage, frequency over limited protection, phase fault, phase lackInput voltage, frequency over limited protection, phase fault, phase lackInput voltage, frequency over limited protection, phase fault, phase lack
Output ProtectionOver current, short circuit, over voltage, low voltageOver current, short circuit, over voltage, low voltageOver current, short circuit, over voltage, low voltage
Battery ProtectionOver charge, over-discharge protectionOver charge, over-discharge protectionOver charge, over-discharge protection
Temperature ProtectionEnvironment over temperature protection, inverter over temperature protectionEnvironment over temperature protection, inverter over temperature protectionEnvironment over temperature protection, inverter over temperature protection
Hardware Fault ProtectionAssistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protectionAssistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protectionAssistant power abnormal, breaker cut off, breaker overload, power devices over current/over voltage etc. protection
GENERAL SYSTEM PARAMETERS
Working EnvironmentTemp: -10 up to 40ºC,
Relative humidity: 30% up to 90%
Altitude less than 2000m (1% decrease against 100m rise, Max. altitude 4000m)
Temp: -10 up to 40ºC,
Relative humidity: 30% up to 90%
Altitude less than 2000m (1% decrease against 100m rise, Max. altitude 4000m)
Temp: -10 up to 40ºC,
Relative humidity: 30% up to 90%
Altitude less than 2000m (1% decrease against 100m rise, Max. altitude 4000m)
Cooling MethodCOMPULSIVE VENTILATIONCOMPULSIVE VENTILATIONCOMPULSIVE VENTILATION
Communication InterfaceRS232 / RS485, optional dry contact, SNMP card (for remote control via internet)RS232 / RS485, optional dry contact, SNMP card (for remote control via internet)RS232 / RS485, optional dry contact, SNMP card (for remote control via internet)
Parallel OperationTandem hot backup or parallel connectionTandem hot backup or parallel connectionTandem hot backup or parallel connection
Auto-surge Capacity10 / 700μS
5KV; 8 / 20μS
20KA
10 / 700μS
5KV; 8 / 20μS
20KA
10 / 700μS
5KV; 8 / 20μS
20KA
Protection LevelIP21IP21IP21
Safety PerformanceVin-n Vout-n 2000Vac, creepage less than 10mA, insulating resistance greater than 2MΩ (500VDC)Vin-n Vout-n 2000Vac, creepage less than 10mA, insulating resistance greater than 2MΩ (500VDC)Vin-n Vout-n 2000Vac, creepage less than 10mA, insulating resistance greater than 2MΩ (500VDC)
Noise (dB)55 up to 6055 up to 6055 up to 60
Dimension (W*D*H) mm980 * 800 * 1800980 * 800 * 1800980 * 800 * 1800
Weight (Kg)570640720

NOTE: Subject to changes without further notice!